| Charging Method |
Constant Voltage Charge |
| Application Type |
Standby & Cycle Use |
| Standby (Float) Voltage |
13.6 – 13.8V |
| Standby Reference Temperature |
25℃ |
| Cycle (Deep Cycle) Voltage |
14.5 – 14.9V |
| Cycle Reference Temperature |
25℃ |
| Maximum Initial Charging Current |
36A |
| Charging Current Limitation |
Do not exceed 36A during initial charge |
| Voltage Tolerance |
±0.1V |
| Temperature Compensation |
Recommended for temperatures above or below 25℃ |
| Suitable Systems |
UPS, Solar Systems, Inverters, Backup Power |
| Overcharge Protection |
Required to prevent battery damage |
| Charging Mode |
Float (Standby) / Boost (Cycle) |
| Safety Note |
Ensure proper ventilation during charging |